WKGY1 High-Voltage Liquid Resistance Soft Starting Cabinet
General of WKGY1
With the development of ecoomy in China, the electric drag equipments of high voltage and large capacit increase gradually, among which the AC drag system of 10KV (6KV) increases rapidly.

For high voltage AC motors with medium and large capacity, the most important problem is starting. Through direct start has many advantages such as easy, economical and short starting time, the starting current (usually 5-7 times the rated current) is big. which causes a serious problem of over current impact on the power network and the motor.lt is proved that even if the capacity of the power network allows direct starting, the heat impact and electro-dynamic impact on the motor caused by direct starting current is very harmful. Because when the motor is directly started, the temperature may increase by ablut 150'C even in about 10 seconds, which tends to damage the motor axis is big. the starting time will be prolonged, then more harm will be caused by the direct start. In addition, some equipments and procedures require smooth start. The direct start may impact and damage the equipment or affect the product quality. Therefore, the starting performance of the motor should be given enough importance.

At present, high voltage motor develops rapidly in China, while the complementary starting devices are rather out of date. The traditional reactor starting with reduced voltage and direct starting can obtain rather large starting torque under the same starting conditions, but they connot meet the requirements of smooth starting and small impact. In addition, the costs are not low enough.

Therefore, we recommend the WKGY1 series high voltage liquid resistor soft starting cabinet, which is to be used in high voltage squirrel cage motors with medium and large capacity.Under certaqin static operation condition, it has the same performance as reactors.Under dynamic operation condition, it can provide non-step continuous starting. Since it makes use of the negative temperature character of the liquid resistor, the voltage of the motor and the starting torque may increase gradually. Therefore, the motor is smoothly started. With silmple structure and high reliability, this system is economical, easy to install, operate and maintain.

WKGY1 series high voltage liquid resistor soft start cabinet is to be applied to many industries such as metallurgy, construction material, mine, petroleum, chemistry, water supply, power industry and so on. It is used to provide heavy starting in various high voltage motors with medium and large capacity such as pumps, fans, compressors.rolling mills, crushers, belt conveyers and so on . It has many features such as small and static current,which is an ideal replacement for traditional reactor starting with reduced voltage and direct starting.
Product Model & Nameplate
WKGY1 Series Principle
The high voltage soft starter is series connected to the main circuit of the squirrel cage motor,and makes use of its balanced three-phase resistor in different temperature.When current is applied to the resistor, the temperature of the resistor increases and the resistor value decreases gradually, so that the voltage of the motor and the starting torque increase gradually and then the purpose of obtaining smooth motor starting and reduced starting current is reached.

The high voltage soft starting cabinet is connected to the motor starting circuit through high voltage switch cabinet (starting control cabinet). This high voltage switch cabinet has many functions such as starting the motor,cutting off the power supply circuit,providing protection to the hgh voltage heat distortion resistor when it finishes the starting process by itself so that the resistor won't be electrified all the time.
Refer to the plan diagram for the main circuit plan of high voltage motor
Technical Parameter of WKGY1
WKGY1 Series Operation & Maintenance Condition
01、Ambient temperture: 0℃ -40℃(The average temperature within 24 hours should not exced 35℃);
02、Relative humidity: no more than 90%;
03、Altitude: no higher than 2000m;
04、The starter should be placd indoors where there is no big vibration or impact;and the vertical gradient should not exceed 5°;
05、No electric dust and corrosive gas is allowed, and it should be placed in the situation without any danger of fire or explosion;
06、The high voltage soft starter cabinet is not applicable in frequentstarting situations. It is allowed to start the motor three time or have an accumulated starting time no more than 120S. The resistor cabinet should be released from the electric circuit after it is used so that it won' t have electricity for a long time;
07、Periodical test should be carried out in order to see whether thereis any unusual condition such as leakage,creepage and so on;
08、An annual test should be carried out to the liquid resistor cabinet with voltage resistance of 42KV.
WKGY1 Series Shape &Installation dimensions
WKGY1 Series Order Instruction
The type, specification and quantity ordered;
The type, power, voltage and current of the motor used;
Names of the equipments used and requirements to the operation conditi-ons;
Main circuit plan of the adopted motor high voltage starting;
Please contact the manufacturer,if there is any special requirement.