WKR5000 Series Motor Soft Starter
Product Model & Nameplate
General of WKR5000 Series Moto Soft Starter
WKR5000 motor soft starter is applicable for three-phase AC squirrel cage asynchronous motors of 5.5kW~600kW and AC 380V~1140V, 50 (60)Hz, rated current 1200A and below, the panel operation display mode not only is convenient for parameter setting and modifying as well as understanding various functions of soft starter for users, but also is convenient for observing the working state of soft starter and motor; it has perfect protection functions for motor starting and running without being equipped with thermal relay; its closed-loop control sharply improves stationarity and reliability of soft torque start and soft torque stop of motor; it employs bypass contactor for running, the operating power consumption is almost zero, this improves its reliability while reducing its volume.

The motor soft starter is of unit type, a circuit breaker (for short-circuit protection) and AC contactor (for bypass after finishing starting) are required to be installed in the cabinet, and form into motor control circuit with the switch.
Service Conditions of soft starter
01、Installation site should be in compliance with the following service conditions and installation methods, otherwise, it is difficult to guarantee the performance of WKR5000 motor soft starter, the service life of soft starter would be reduced, the soft starter even would be damaged.
02、Mains voltage: AC 380V-1140V, 50/60HZ.
03、Applicable motor: squirrel cage three-phase asynchronous motor, rated power of motor should be matched with the rated power of soft starter.
04、Starting frequency: not over 15 times per hour.
05、Cooling mode: natural air cooling。
06、Degree of protection: IP20
07、Ambient temperature: -30 ℃ ~+55 ℃
08、Ambient humidity: relative humidity not exceed 95%, no condensation
09、Service place: draughty, free of corrosive gas or conductive dust, vibration should be lower than 0.5G.
10、Altitude: <3000m, if the altitude exceeds this height, please improve the power of soft starter correspondingly.
Applicable Industry
Water pump-makes use of water hammer phenomenon releasing pump during soft stop, saves system maintenance cost.
Ball mill-makes use of the ramp voltage start to reduce wear of gear torque and maintenance workload, it not only saves time, but also saves cost.
Fan-reduces belt wear and mechanical shock, saves maintenance cost.
Compressor-makes use of rotation-clogging protection and quick protection functions, preventing from motor burn out due to overheating caused by mechanical failure or block.
Transfer mechanism-realizes smooth starting through soft start, preventing product displacement or overflowing of liquid.
List of WKR5000 Series Moto soft Starter
Parameter setting & Description
Notes:
1、In setting state, if there isn't any key operation for over 2min, it would exit the setting state automatically.
2、Operation of parameter setting can be carried out in any state except soft start or soft stop state.
3、 Push down YES to start up, you are able to get back the set parameters (except PD) to default value.
Wiring method & External control terminals
WKR5000 series motor soft starter has two types of wiring method:
Wiring of main loop: including wiring of three-phase power inputting/outputting main motor, wiring of circuit breaker and bypass contactor.
Wiring of control terminal: there are 12 miniature connection terminals for leading out, including the control line of bypass contactor, control line of ON/OFF switch, and analog output signal line.
Wiring schematic drawing of main loop of moto soft starter
Secondary standard comection
External terminals desciption of moto soft starter
Terminals 1 and 2 are of passive normally open contacts, used for controlling of bypass contactor, they will close after successful start.
Terminals 3 and 4 are for programmable time delay output, output function and mode are determined by the set item PD, they are passive contacts.
Terminals 5 and 6 are for fault output, they will close when the motor soft starter comes across troubles or power failure, and open in normal condition, they are power contacts.
Terminals 7, 8, 9 and 10: form into the external control circuit; they are passive contacts.
Terminal 10 is a common port
Terminal 7 is for instantaneous stop input: when 7 is disconnected from 10, motor soft starter stops working. (Used for connecting with thermal relay NC)
Terminal 8 is for soft stop input: when 8 is disconnected from 10, it is soft stopped. (Need not autolocking)
Terminal 9 is for soft start input: when 9 is connected with 10, it is soft started.(Need not autolocking)
The above wirings are of three-wire control mode, when terminals 8 and 9 are connected in parallel and used as one terminal, they are able to start once connecting with 10, and stop once breaking, they can be applied to a relay contact to control start/stop, this is two-wire control
Terminals 11 and 12 are 0~20mA DC analog output, max output resistance is 300Ω.